2.1.1 WATER RESISTIVE BARRIER (WRB).
Should be installed complying with IBC Sections 1404.2 and 2510.6 or IRC Sections R703.2 and R703.6.3. One Layer or Two Layer of No.15 asphalt felt, free from holes and breaks, complying with ASTM D 266 for Type 1 felt or other approved water-resistive barrier shall be applied over studs or sheathing of all exterior walls. It should be attached horizontally starting at the bottom and overlap not less than 2″. Overlap the vertical joints by at least 6″. If using flashing or support brackets (anchors), install them before proceeding to the next step.
2.1.2 FLASHINGS.
Flashings must be installed in compliance with IBC Sections 1405.4 and 1405.10.1.12 or IRC Sections R703.8 and R703.12.2. All Flashings must be corrosion resistant materials and integrated with Water Resistive Barriers (WRB). Flashings must be installed at wall penetrations and terminations of Adhered Stone Veneer installations.
2.1.3 WEEP SCREED.
Weep Screeds must comply with and be installed in accordance with IBC Section 25.1.2 or IRC Section R703.6.2.1, as applicable. In addition weep Screed must be of corrosion resistant metal, min 0.019 inches or min No. 26 gage, or a plastic weep screed min 0.05”, weep holes with a min diameter of 3/16” (4.8 mm) spaced at a max of 33 inches (838 mm) on center and with a minimum vertical attachment flange of 3 ½” wide, which is referenced in IBC Section 1405.10.
2.1.4 LATH.
Studs must be spaced no more than 16” (406mm) on center. Lath must be a corrosion-resistant,
self-furred, 2.5lb/yd2 (1.4kg/m2), galvanized, expanded metal lath in compliance with ASTM C 847.
Lath must be fastened to the wall framing in accordance with the minimum requirements of Section
7.10 of ASTM C 1063 or IRC Section R703.6.1, as applicable. Fasteners must be spaced a maximum of
6 inches (152mm) on center, must penetrate minimum ¾ inch into wood framing members and a minimum of 3/8 inch (9,5mm) through steel members. At corners, overlap the vertical jionts at least 16″ around the corners cracking.